Danfoss turns refrigerators into ovens

Article by Nacata Security, 14/10/2026

Did you know that your supermarket’s thermostat could be an attacker’s entry point?

Critical vulnerabilities in Danfoss controllers are being actively exploited.

The Danfoss AK-SM 800A is the centralized brain governing all refrigeration circuits in a commercial facility, accessible through a web interface.

Claroty Team82 documented in August 2026 how to chain three vulnerabilities to bypass authentication, execute remote commands, and fully manipulate the system’s operation.

Illustrates the CVE-2025-41450 mechanism: a hidden alternative authentication path that generates a daily code and allows administrative access without knowing the actual password.
Passwordless access

The attack chain begins with an invisible backdoor.

CVE-2025-41450 affects versions of the AK-SM 800A prior to 4.2. The vulnerability is not a weak password: the firmware includes an alternative mechanism called check_code_of_day that generates a code calculated from the device’s date. Anyone who knows the algorithm can reproduce it and obtain a full administrative session without ever knowing the device’s actual password.

With administrator access, the next step is command execution.

CVE-2025-41451 turns the SMTP password field in the email configuration into an operating system command injection point. The application builds a system command by concatenating that value without neutralizing special shell characters. An authenticated attacker can go from adjusting email parameters to executing arbitrary commands on the device, without installing any prior implant.

Two conventional software flaws, real physical consequences for food products.

A third vulnerability, CVE-2025-41452, allows replacing the embedded web server configuration and reloading Nginx, generating a denial-of-service condition on the administration interface. Losing that interface complicates monitoring and incident response, even though the physical circuits continue operating according to their local design.

Illustrates CVE-2025-41451: the SMTP configuration field acting as an operating system command injection point, turning an email setting into remote code execution.
Command injection

Thousands of devices directly exposed to the Internet.

Claroty Team82 identified approximately 2,765 publicly accessible AK-SM management interfaces on Censys. Not all of them are vulnerable or compromised, but they are reachable without needing to first gain access to any supermarket’s corporate network.

A French incident puts it in real context.

In the early hours of October 11–12, 2026, more than 150 French supermarkets — including Intermarché, Coopérative U, and E.Leclerc — suffered a sabotage attack that raised refrigeration temperatures to 50 °C. Tons of food had to be discarded due to cold chain failure. The technical chain documented by Claroty is a plausible hypothesis, though without public confirmation.

CERT-FR has already issued urgent recommendations after detecting active compromises.

The French agency detected numerous compromises of Danfoss AK-SM and AK-SC units and recommends filtering connections to allow only authorized vendor access, restoring devices to factory settings when intrusion is suspected, applying available patches, rotating credentials, reviewing accounts, and reconfiguring the devices.

Illustrates the scale of the problem: thousands of management interfaces publicly exposed on the Internet, with the French incident as a real-world consequence.
Massive global exposure

Danfoss has already published fixes: version R4.3.1 closes the vulnerabilities.

CVE-2025-41450 is remediated by updating to version 4.2 or later; CVE-2025-41451 and CVE-2025-41452 are closed in version R4.3.1. Danfoss published the corresponding advisories and recommends not exposing management interfaces directly to the Internet.

Updating is not enough if the system has already been compromised.

Before restoring, preserve available logs and evidence. Then verify that the operational configuration is legitimate, check the integrity of the devices, and physically validate temperatures and alarms with the responsible personnel. Team82 also advises restricting administrative access to trusted networks or connections protected by VPN.

A refrigeration controller can be a weapon.

If the remote maintenance web interface can become the entry point into a physical process, do you have real visibility into which systems in your organization are exposed?

What to do now

  • ✓Update the AK-SM 800A firmware to R4.3.1.
  • ✓Remove Danfoss management interfaces from Internet exposure.
  • ✓Review accounts, rotate credentials, and physically validate temperatures and alarms.

Do you know how many industrial controllers in your organization are exposed right now?

Security is not improvised, it is audited. At Nacata Security we detect vulnerabilities and protect your company, because a single flaw can cost you everything you have built.

Related articles

Nacata Security, reach out to us anytime

How would you rate this news?

We are Nacata Security, get to know us

web: nacata.io

email: info@nacata.io

Phone: 919930793

LinkedIn: Nacata Security

Threats

Risks and attacks happening right now: vulnerabilities being actively exploited, official alerts from cybersecurity agencies, ongoing phishing or malware campaigns.

Information meant to help you act and protect yourself before the problem reaches you.



RATING


8



Who are we?


At Nacata Security we are an offensive cybersecurity company specialized in audits and penetration testing.


We detect, assess and help mitigate the vulnerabilities of your systems, networks and applications before a real attacker exploits them, offering 360º defense tailored to each client.


We’d be glad to get in touch with you for whatever you need.